The sensor must not be used in potentially explosive atmospheres.
Performance features
- External sensor for the gas detectors GX-A1 and GX-HS
- Detection for LNG, town gas, natural gas, (methane) and liquid gas (propane/butane), R290
The external sensor is suitable for the gas detectors GX-A1 and GX-HS and is connected via an RJ connector on the cable.
The connecting cable of the sensor can be extended.
The following minimum cross-sections result as a function of
on the length of the line:
Cable cross section 3 x 0.14 mm²: maximum length 20 m
Cable cross section 3 x 0.5 mm²: maximum length 50 m
Scope of delivery
- Gas sensor GX-LNG
- Instructions for use
- Mounting material
U-sensor output
- 0 % - 1.0 Volt
- 10 % - 1.6 Volt
- 20 % - 2.3 Volt
- 30 % - 2.9 Volt
Technical details
Operating voltage: | 5 V -24 V DC |
Current consumption | max. 175 mA |
Sensor output voltage | 1- 4,5 V |
Heating current | 175 mA |
Sensor type: | catalytic |
Humidity (ambient): | 5-90 % RH (non-condensing) |
Functional area: | -10 °C / +50 °C |
Storage temperature: | -20 °C / +70 °C |
Lifespan: | approx. 5 years |
Protection class: | IP 20 |
Cable length: | 2,5 m |
Cable Ø: | 3.5 mm |
Dimensions (HxWxD): | 52x27x29 mm |
WEEE NO.: EN91394868