Monitoring device for safety shutdown of the boiler in case of carbon monoxide leakage. Alarm threshold: 50 ppm CO according to DIN EN 50 291-1
This device is designed to protect people from the topical effects of carbon monoxide contact. Lifetime CO sensor max: approx. 6 years (max. 40°C, min. 40% rH), approx. 10 years (max. 28°C, 30% rH).
Important warnings:
The following substances can influence the CO detector and possibly trigger a false alarm. Therefore, they must not be used in the room where CO detector is installed: ethylene, ethanol, alcohol, iso-propanol, gasoline, toluene, ethyl acetate, hydrogen, hydrogen sulfide and sulfur dioxides. Individuals with specific medical conditions may not be adequately protected by the CO detector and should use a warning device that produces audible and/or visible signals at carbon monoxide concentrations as low as 50ppm. If in doubt, consult a physician.
Performance features
- Double safety through acoustic and optical warning function and automatic shutdown of the connected appliance in case of gas leakage
- Detection of carbon monoxide (CO) according to DIN EN 50291 TÜV-tested
- Regular automatic self-test function
- intelligent self-test, long-life electrochemical sensor, test button and more.
Possible applications
- for gas heaters, gas heating, gas cookers, gas furnaces, oil heating and any combustion facility with supply
- CO sensor service life max: approx. 6 years (max. 40°C, min. 40% rH), approx. 10 years (max. 28°C, 30% rH)
Scope of delivery
- CO detector
- 2 keyholes on rear wall, 2 screws/dowels each enclosed
Technical data
Electrical connection: | 24 Volt DC (+/- 10 %) |
Mechanical connection: | RJ12 socket, 6-pin, 3 of them occupied |
Power consumption: | 29 - 31 mA in monitoring mode |
38 - 41 mA in alarm mode | |
max. 46 mA in test mode | |
Optical display: | 3 LEDs, green (operation), yellow (error), red (alarm) |
Audible indication: | Built-in piezo, resonant frequency 4.4 kHz, 85 dB(A) @ 1 m |
Alarm thresholds / delay: | 50 ppm CO according to DIN EN 50291 |
Output signal: | PWM on open collector: 19.3 - 20.8 Hertz, nominal 20 Hz, |
Hi 3 - 7 ms (Operation), Lo 8 - 12 ms (Alarm), Hi 23 - 27 ms (Error) | |
Protection class | II |
Protection class: | IP20 according to EN 60529 |
Lifetime | approx. 10 years |
Temperature range: | 0 ... 40°C, short time max. 45°C |
Humidity: | max. 90% rel. Hg, non-condensing |
Sensor element: | Figaro TGS 5042-A00, electrochemical, typ. 1.2 - 2.4 nA / ppm |
Evaluation: | digital, OP-AD-DA, quasi-linear after calibration +/- 1% |
Dimension (H x W x D) / Weight: | 88 x 58 x 38 mm / 91 g |
WEEE NO.: EN91394868
Reviews
There are no reviews yet