CO sensor, measuring cell, evaluation and software were subjected to a complex full test according to DIN EN 50291 at TÜV Süd, safety and stability were certified for the system. The professional CO warning system GX-C300 has an internal electro-chemical CO sensor, which provides extremely precise values of the CO concentration. These are shown on a plain text display and processed in a powerful 32-bit microcontroller. The actual alarm is loud with an integrated piezo, the display flashes and a potential-free alarm relay switches. The installation is very simple: The bottom part of all C300 systems contains the screw terminals for the power supply and the two relays and is screwed to a wall in the room to be monitored. In this way, the installation can be retained if, for example, a sensor is replaced, because the sensor, display, μController and evaluation electronics are located in the cover alone, which is simply unplugged.
Performance features
- Acoustic and optical warning
- High-precision CO measurement and ppm-accurate display
- 2 potential-free changeover relays 5 A, one each for alarm and fault, perfect for building management systems
- Intelligent sensor system to avoid false alarms
- Continuous monitoring, storage and display of operating parameters in plain text display
- Switching off the source of danger in the event of an alarm
- Integrated switching power supply for low power consumption
- Alarm thresholds easily adjustable at the factory according to your specifications, e.g. 30ppm instant alarm in shisha bar
Possible applications
- Monitoring of combustion sites / gas heaters in case of carbon monoxide (CO) leakage
- Guest room surveillance in shisha bars and smoking clubs
- Monitoring of staircases and escape routes in small private underground garages
- Open fireplaces in gastronomy, canteens and mobile kitchens
- Heating and utility rooms all dry indoor rooms with combustion facilities
Technical data
Operating voltage: | 100 - 240 V AC / 50-60 Hz |
Performance record: | max. 6 VA, depending on operating condition |
Sensor technology: | electrochemical |
Relay contact alarm Re1: | 250 V~ AC / 5 A (potential-free changeover contact) |
Relay contact fault Re2: | 60 V= DC / 5 A (potential-free changeover contact) |
Sound pressure control unit: | 85 dB(A) (100 cm distance) |
Software version control unit / sensor: | X0.82 |
Functional area control unit: | -15°C ... +45°C / 10 ... 90% rH, non-condens. |
Functional area sensor: | 0°C ... 60°C / 10 ... 90% rH, non-condensing |
Lifetime* Sensor max: | 6 years @ max. 40°C + min. 40% rH |
10 years @ max. 28°C + min. 30% rH | |
Protection class: | IP 20 |
Dimensions control unit: | 80x160x55 mm (HxWxD) |
WEEE NO.: EN91394868
Reviews