All gas-powered devices have the potential to release dangerous gas. As soon as the GXHS gas detector detects such gases, it automatically interrupts the power supply and, optionally, the gas supply through the gas line. Depending on the type of sensor connected, the device detects town gas and natural gas (methane/butane), coolants and refrigerants, or carbon dioxide used in the catering industry or from the air we breathe. The GX-HS device features an output for an external buzzer. The input also offers two setting options (via wire jumper). The triggered alarm can be saved and acknowledged by pressing a button. The alarm can also be automatically cleared when the gas concentration falls below a certain threshold.
Gas sensor connection: Only one gas sensor can be connected to the GX-HS gas detector at a time. https://youtu.be/oTxMdmamv_M
Areas of application
- Detection of town, natural and liquefied gases (GX-SE)
- Indoor air (GX-CO2-25 and GX-DS)
- Gastronomy CO2 monitoring (GX-CO2-30)
- Air conditioning systems, fluorinated refrigerants (GX-CFC)
- Only one sensor can be connected to a GX-HS 24V
Applications depending on the sensor
type
|
Gases
|
Ref. No.
|
GX-SE |
Town and natural gas (methane, butane, propane) |
200897 |
GX-CFC |
Chlorofluorocarbons, refrigerant R-32, etc. |
200901
|
GX-DS |
Carbon dioxide, indoor air quality, simple |
200884 |
GX-CO2-25 |
Carbon dioxide, indoor air quality, with test function |
200989
|
GX-CO2-30 |
Carbon dioxide from processes and technical facilities |
300315 |
GX-CO |
Carbon monoxide, smoke gases |
200898
|
Accessories can be found under: Warning Systems Accessories
Features
- optical warning (LED)
- 1 connection for a gas sensor
- Housing for 35mm standard DIN rail system
- Height placement of the external sensor possible independent of the mounting height of the control unit
- Can be used for different gases depending on the sensor
- Cable break detection for sensor cable
- 2 integrated switching relays 5 A (potential-free changeover contacts), connection to BUS system (EIB) or external devices, as well as switching off gas consumers
Technical data
Operating voltage |
230 V~ 50 Hz |
Power consumption |
3 - 5 VA, depending on operating condition |
Relay contact |
2 changeover contacts NC/NO (potential-free) |
Switching capacity |
max. 5 A / 230 V |
Sensor connection |
1 |
Sensor voltage |
5 V |
Buzzer connection |
9 - 12 V= / 50 mA |
Functional area |
-15 °C / +40 °C |
Protection class |
IP20 |
Dimensions (HxWxD) |
57 x 72 x 90 mm |
Connection example