View full detailsThe FTX sensor monitors the flue gas temperature in the flue pipe and detects whether the stove is in operation. If the defined temperature limit of 40°C is exceeded, the system blocks the exhaust air release – the chimney takes priority. If the temperature drops by approximately 15°C, the release signal is sent again.
The integrated window transmitter allows the exhaust air system to operate only when the window is open— unless the furnace is cold , in which case it is automatically enabled. This dual logic (temperature + window contact) significantly increases safety and ease of use.
The components are already programmed at the factory – unpack, assemble, done!
FTX sensor for smoke pipes from Ø 120 mm
Permissible ambient temperature sensor max. 180 °C
Transmitter installation outside the heat area (max. 50 °C)
Radio range: approx. 20 m in open field
Operation only suitable for single ovens
A notice:
The included FDS 200 wireless exhaust air control is DIBt-certified —this does not apply to the entire set. Please coordinate the planned installation with your local chimney sweep well in advance. Regional requirements may vary.
The FTX wireless temperature transmitter may only be operated with a single oven .
Use on several fireplaces at the same time is not technically permitted , as safe operation cannot be guaranteed.
👉 In this case, please contact the technical support of Elektrotechnik Schabus – we will find an individual solution for your situation.
Would you like to be able to choose between two windows ? No problem:
With a second window contact transmitter FDS 098 (programmed to the same code at the factory), an OR function can be implemented – an open window is sufficient to release the exhaust air system.
Do you need two separately switchable outputs ?
An additional receiver (installation: FDS 199 , intermediate plug: FDS 299 ) can be added to the existing set.
As soon as the oven is cold or a window is opened , both receivers release their connected devices.
For this purpose, Elektrotechnik-Schabus needs the serial number to code the devices to each other.
👉 When ordering additional devices, please always state the serial number of your existing receiver .
WEEE NO.: DE91394868Protection class | IP40 |
---|---|
battery | CR2023/ 3 V |
Line | 2 m (4-wire) | Silicone | max. 180°C |
Assembly | 3 holes in the flue pipe, specialist company |
Switching differential | approx. 15 K, hysteresis |
Switching accuracy | +/- 7 K |
Switching point | 40° C, factory set |
Technical data of related articles | 300462 FDS 200 |
temperature | max. 180 °C cable temperature, max. 180 °C ambient temperature, max. 50 ° at the transmitter, max. 500 °C sensor temperature |
Time | < 45 seconds response time |
The FTX sensor monitors the flue gas temperature in the flue pipe and detects whether the stove is in operation. If the defined temperature limit of 40°C is exceeded, the system blocks the exhaust air release – the chimney takes priority. If the temperature drops by approximately 15°C, the release signal is sent again.
The integrated window transmitter allows the exhaust air system to operate only when the window is open— unless the furnace is cold , in which case it is automatically enabled. This dual logic (temperature + window contact) significantly increases safety and ease of use.
The components are already programmed at the factory – unpack, assemble, done!
FTX sensor for smoke pipes from Ø 120 mm
Permissible ambient temperature sensor max. 180 °C
Transmitter installation outside the heat area (max. 50 °C)
Radio range: approx. 20 m in open field
Operation only suitable for single ovens
A notice:
The included FDS 200 wireless exhaust air control is DIBt-certified —this does not apply to the entire set. Please coordinate the planned installation with your local chimney sweep well in advance. Regional requirements may vary.
The FTX wireless temperature transmitter may only be operated with a single oven .
Use on several fireplaces at the same time is not technically permitted , as safe operation cannot be guaranteed.
👉 In this case, please contact the technical support of Elektrotechnik Schabus – we will find an individual solution for your situation.
Would you like to be able to choose between two windows ? No problem:
With a second window contact transmitter FDS 098 (programmed to the same code at the factory), an OR function can be implemented – an open window is sufficient to release the exhaust air system.
Do you need two separately switchable outputs ?
An additional receiver (installation: FDS 199 , intermediate plug: FDS 299 ) can be added to the existing set.
As soon as the oven is cold or a window is opened , both receivers release their connected devices.
For this purpose, Elektrotechnik-Schabus needs the serial number to code the devices to each other.
👉 When ordering additional devices, please always state the serial number of your existing receiver .
WEEE NO.: DE91394868Protection class | IP40 |
---|---|
battery | CR2023/ 3 V |
Line | 2 m (4-wire) | Silicone | max. 180°C |
Assembly | 3 holes in the flue pipe, specialist company |
Switching differential | approx. 15 K, hysteresis |
Switching accuracy | +/- 7 K |
Switching point | 40° C, factory set |
Technical data of related articles | 300462 FDS 200 |
temperature | max. 180 °C cable temperature, max. 180 °C ambient temperature, max. 50 ° at the transmitter, max. 500 °C sensor temperature |
Time | < 45 seconds response time |